A proven concept
has been used for the new, systemcompatible single-output and dual-output power supplies of the TOE 8840 and TOE 8850 series.
Exceptional specifications are achieved with a total output power of 160 W or 320 W as a result of the classical in-phase control principle.
A total of 22 different models deliver voltages up to 130 V and currents up to 20 A. With a resolution of 12 bits in the voltage and current ranges, a simple and convenient user interface, and the excellent specifications, these instruments are suitable for both manual and busbased modes.
Integrated measurements
A further significant characteristic is the high-resolution measurement of the voltage and current values; these are output on 4-digit LED displays and can be read at a high rate in bus mode.
This means that additional measuring instruments are usually superfluous.
Adjustment using incremental spinwheels
The output values are adjusted with a selectable sensitivity using wear-free incremental spinwheels, thus permitting reliable and precise adjustment of the output voltage and current even after many years of service.
Remote control (option)
All instruments can be remote-controlled in analog mode as well as via GPIB and RS 232 interfaces using the SCPI command set (SCPI: Standard Commands for Programmable Instruments). The system interfaces are characterized by a high response and measuring rate. In addition, instrument driver software is available under “LabView“.
Automatic calibration
Fast and convenient calibration of all output parameters is possible externally within a few minutes without any adjustment of trimmers or interventions in the instrument. This “software calibration“ can be carried out simply using the control elements or supported by a computer within a test system. The “software calibration“ provides an advantage which should not be underestimated when considering the regular calibration intervals which are becoming increasingly important in quality assurance systems.
Voltage or current source
Depending on the values set for the voltage and current, each power supply can be operated as a voltage source or a current source depending on the load conditions. All outputs can be connected in parallel or series without problem.
High performance and exemplary operating characteristics
Special features
Output 1 | Output 2 | ||||
Model | Voltage | Current | Voltage | Current | Power |
Single-output power supplies TOE 8851-16 TOE 8851-24 TOE 8851-32 TOE 8851-40 TOE 8851-64 TOE 8851-130 |
0 - 16 V 0 - 24 V 0 - 32 V 0 - 40 V 0 - 64 V 0 - 130 V |
0 - 20 A 0 - 13 A 0 - 10 A 0 - 8,0 A 0 - 5,0 A 0 - 2,5 A |
– – – – – – |
– – – – – – |
320 W 320 W 320 W 320 W 320 W 320 W |
Double-output power supplies TOE 8852-16 TOE 8852-24 TOE 8852-32 TOE 8852-40 TOE 8852-64 TOE 8852-130 |
0 - 16 V 0 - 24 V 0 - 32 V 0 - 40 V 0 - 64 V 0 - 130 V |
0 - 10 A 0 - 6,5 A 0 - 5,0 A 0 - 4,0 A 0 - 2,5 A 0 - 1,2 A |
0 - 16 V 0 - 24 V 0 - 32 V 0 - 40 V 0 - 64 V 0 - 130 V |
0 - 10 A 0 - 6,5 A 0 - 5,0 A 0 - 4,0 A 0 - 2,5 A 0 - 1,2 A |
2 x 160 W 2 x 160 W 2 x 160 W 2 x 160 W 2 x 160 W 2 x 160 W |
Tracking function
The automatic tracking mode with dualoutput power supplies means that it is possible to control the output voltage of output 2 as a function (0 % to 100 %) of output 1 with retention of all control properties.
Remote control
Command syntax in accordance with IEEE 488.2 with command set switchable between compatible TOELLNER commands and SCPI commands.
GPIB interface (option)
Interface connection in accordance with IEEE 488.1; electrically isolated from main outputs. The device address can be set as desired per menu.
Setting rate: approx. 25 settings/s
Measuring rate: approx. 20 measurements/s
RS 232 interface (option)
9-pin D-SUB connector; electrically isolated from the main outputs. Transfer: half-duplex mode, asynchronous; 110 to 19200 baud adjustable permenu.
Setting rate: approx. 20 settings/s
Measuring rate: approx. 15 measurements/s
Additional functions
These modern, proven and exceptionally well equipped power supplies are additionally characterized by supplementary functions such as the saving of 100 instrument settings, the standby circuit for the power outputs, sense and tracking modes.
Price and performance
In addition to the exceptional specifications and characteristics, all power supplies of the TOE 8840 and TOE 8850 series have a remarkable price/performance ratio.
Common operating functions
Anzeige Voltage und Current:
Display of voltage and current: separately on two 4-digit displays for all single instruments; on two selectable 4-digit V/A displays for the dual instruments. Constant voltage or constant current mode is indicated by single LEDs.
Sense mode can be selected directly. Connection to front or rear of instruments.
Nonvolatile memory for 100 complete instrument settings and the last setting when switching-off.
Special features
Outputs
Single-output power supplies Model |
TOE 8851-16 | TOE 8851-24 | TOE 8851-32 | TOE 8851-64 | TOE 8851-130 | |
Output data | Voltage Current |
0 - 16V 0 - 20 A |
0 - 24 V 0 - 13 A |
0 - 32 V 0 - 10 A |
0 - 64 V 0 - 5 A |
0 - 130 V 0 - 2.5 A |
Setting resolution | Voltage Current |
10 mV 10 mA |
10 mV 10 mA |
10 mV 5 mA |
20 mV 2 mA |
100 mV 1 mA |
Setting accuracy | Voltage Current |
0.1 % + 10 mV 0.2 % + 20 mA |
01 % + 10 mV 0.2 % + 10 mA |
01 % + 10 mV 0.2 % + 10 mA |
01 % + 20 mV 0.2 % + 4 mA |
01 % + 100 mV 0.2 % + 2 mA |
Deviation in regulation with 100 % change in load |
Voltage Current |
5 x 10-5 5 x 10-5 |
5 x 10-5 5 x 10-5 |
5 x 10-5 10-4 |
5 x 10-5 2 x 10-4 |
10-4 5 x 10-4 |
With change in line voltage ± 10 % |
5 x 10-5 | 5 x 10-5 | 5 x 10-5 | 5 x 10-5 | 5 x 10-5 | |
Regulation time with change in load from 20 % to 100 % Tolerace: 0.2 % Urated |
< 200 μs | < 100 μs | < 80 μs | < 80 μs | < 80 μs | |
Residual ripple (10 Hz - 1 MHz) | Voltage Current |
0.5 mVrms 100 mArms |
0.5 mVrms 500 μArms |
0.5 mVrms 500 μArms |
1 mVrms 200 μArms |
2 mVrms 100 μArms |
Measure accuracy | Voltage Current |
0.1 % + 20 mV 0.2 % + 20 mA |
0.1 % + 20 mV 0.2 % + 20 mA |
0.1 % + 20 mV 0.2 % + 10 mA |
0.1 % + 40 mV 0.2 % + 4 mA |
0.1 % + 200 mV 0.2 % + 2 mA |
Temperature coefficient | Voltage Current |
10-4/K 10-4/K |
10-4/K 10-4/K |
10-4/K 10-4/K |
10-4/K 10-4/K |
10-4/K 10-4/K |
Dual-output power supplies Model |
TOE 8852-16 | TOE 8852-24 | TOE 8852-32 | TOE 8852-64 | TOE 8852-130 | |
Output data | Voltage Current |
2 x 0 - 16V 2 x 0 - 10 A |
2 x 0 - 24 V 2 x 0 - 6.5 A |
2 x 0 - 32 V 2 x 0 - 5 A |
2 x 0 - 64 V 2 x 0 - 2.5 A |
2 x 0 - 130 V 2 x 0 - 1.2 A |
Setting resolution | Voltage Current |
10 mV 5 mA |
10 mV 2 mA |
10 mV 2 mA |
20 mV 1 mA |
100 mV 1 mA |
Setting accuracy | Voltage Current |
0.1 % + 10 mV 0.2 % + 10 mA |
01 % + 10 mV 0.2 % + 10 mA |
01 % + 10 mV 0.2 % + 4 mA |
01 % + 20 mV 0.2 % + 2 mA |
01 % + 100 mV 0.2 % + 2 mA |
Deviation in regulation with 100 % change in load |
Voltage Current |
5 x 10-5 10-4 |
5 x 10-5 2 x 10-4 |
5 x 10-5 2 x 10-4 |
5 x 10-5 5 x 10-4 |
10-4 10-3 |
With change in line voltage ± 10 % |
5 x 10-5 | 5 x 10-5 | 5 x 10-5 | 5 x 10-5 | 5 x 10-5 | |
Regulation time with change in load from 20 % to 100 % Tolerace: 0.2 % Urated |
< 100 μs | < 80 μs | < 80 μs | < 80 μs | < 80 μs | |
Residual ripple (10 Hz - 1 MHz) | Voltage Current |
0.5 mVrms 500 μArms |
0.5 mVrms 300 μArms |
0.5 mVrms 200 μArms |
1 mVrms 100 μArms |
2 mVrms 50 μArms |
Measuring accuracy | Voltage Current |
0.1 % + 20 mV 0.2 % + 10 mA |
0.1 % + 20 mV 0.2 % + 10 mA |
0.1 % + 20 mV 0.2 % + 4 mA |
0.1 % + 40 mV 0.2 % + 2 mA |
0.1 % + 200 mV 0.2 % + 2 mA |
Temperature coefficient | Voltage Current |
10-4/K 10-4/K |
10-4/K 10-4/K |
10-4/K 10-4/K |
10-4/K 10-4/K |
10-4/K 10-4/K |
Main outputs | Floating and electrically isolated from the system interfaceace |
Insulation | ± 250 V against ground |
Output sockets | On front of instrument and optionally at rear Standby-circuit of power outputs directly selectable. |
Line voltage | 115 V/230 V ± 10 %, 47 Hz to 63 Hz |
Power consumption | Approx. 730 VA |
Protective measure | Protection class 1 in accordance with DIN 57411/VDE 0411 Part 1/IEC 348 |
Operating temperature | 0 °C to 40 °C |
Storage temperature | -20 °C to 70 °C |
Reference temperature | 23 °C |
Warm-up time | 30 min |
Dimensions (BxHxT) | 265 x 147 x 437 mm |
Weight | Approx. 15 kg |
Housing | Aluminium |
Incremental spinwheel:
Safety/protective measures
Single-output power supplies 320 W
TOE 8851-16 | Power supply | 16 V / 20 A |
TOE 8851-24 | Power supply | 24 V / 13 A |
TOE 8851-32 | Power supply | 32 V / 10 A |
TOE 8851-40 | Power supply | 40 V / 8 A |
TOE 8851-64 | Power supply | 64 V / 5 A |
TOE 8851-130 | Power supply | 130 V / 2.5 A |
Dual-output power supplies 2 x 160 W
TOE 8852-16 | Power supply | 2 x 16 V / 10 A |
TOE 8852-24 | Power supply | 2 x 24 V / 6,5 A |
TOE 8852-32 | Power supply | 2 x 32 V / 5 A |
TOE 8852-40 | Power supply | 2 x 40 V / 4 A |
TOE 8852-64 | Power supply | 2 x 64 V / 2,5 A |
TOE 8852-130 | Power supply | 2 x 130 V / 1.2 A |
Options
Single-output Power supply
Interfaces
TOE 8861/015 | Remote control GPIB and RS 232 |
TOE 8861/016 | Analog remote control |
TOE 8861/017 | Floating analog remote control |
TOE 8850/252 | Output at rear |
Dual-output Power supply
Interfaces
TOE 8862/015 | Remote control GPIB and RS 232 |
TOE 8862/016 | Analog remote control |
TOE 8862/017 | Floating analog remote control |
2 x TOE 8850/252 | Output at rear |
Supplied accessories
Free basic driver for LabViewTM found at the buttom.